Home >  Products > Data Center Infrastructure > Precision Cooling> Room Precision Cooling> MatrixAir TM Series
MatrixAir TM Series
The MatrixAir™ precision cooling system has been developed to meet the increasing demand for ultra-efficient and large capacity. It is a room-based cooling system that can deliver efficient, precise, reliable control of room temperature, humidity and airflow for the proper operation of critical electronic equipment. A wide range of standard units offered from 25 KW to 300 KW in upflow & downflow configurations.

Patent fan design can save up to 30% energy when compared with competitor units, helping data center facilities deliver best-in-class PUEs. Optional cooling source boosts cooling system availability and reliability!


General Features

● Total cooling capacity: 25kW~300kW

● Power-saving and environment-friendly technology

● First class components make MatrixAir more stable

● 7 kinds of cooling types

● Many components can be replaced with different type according customer’s requirement

● Modular structure design eases the transportation 、installation and services

● Patent fan design can reduce 30% energy. The fan supports sinking deployment and non-sinking deployment

● R407 refrigerant, and also compatible with R22 refrigerant (low cost)

● Fluorine pump can save more than 50% energy by using nature cold source

Technical Specification
Air MT***UD Unit 25 30 35 45 55 40 50 60 70 80 90 100
Water MT***
AC Fan  
Air volume m³/h 7500 8000 8500 13000 15000 12500 14000 18000 18500 21000 23000 25000
DX Total Cooling
 Capacity 
kW 26.7 30.8 35.5 45.5 54.5 41.2 53.5 61.4 70.9 81.3 90.6 104.4
DX Sensible Cooling
 Capacity 
kW 24.3 29.3 32.7 42.8 51.8 37.9 49.2 57.7 63.8 77.2 83.4 95
DX Sensible heat raio / 0.91 0.95 0.92 0.94 0.95 0.92 0.92 0.94 0.9 0.95 0.92 0.91
CW  Total Cooling
 Capacity 
kW 27.6 32.4 41.2 56.5 61.5 54.5 59.3 67.4 71 90.6 97.6 106.6
CW Sensible Cooling
 Capacity 
kW 25.3 29.3 36.6 50.2 55.6 47.8 53.5 60.5 64.1 80.8 87.9 94.8
CW Sensible heat raio / 0.92 0.9 0.89 0.89 0.9 0.88 0.9 0.9 0.9 0.89 0.9 0.89
Water flow capacity m3/h 4.75 5.58 7.13 9.75 10.53 9.33 10.14 11.55 11.99 14.03 16.8 18.21
Pressure drop Kpa 51.6 75.3 93.3 85.5 99 77.6 92.2 62.2 68 97.4 104.8 124.1
EC Fan  
Air volume m³/h 7800 8300 8800 13500 15400 13200 14600 18700 19300 21600 23900 26000
DX Total Cooling
 Capacity 
kW 26.9 31.2 35.7 45.9 54.7 41.6 53.8 61.7 71.1 81.8 90.8 104.7
DX Sensible Cooling
 Capacity 
kW 25 30 33.6 44.1 52.5 39.5 50.6 59.2 66.1 78.5 85.4 97.4
DX Sensible heat raio / 0.93 0.96 0.94 0.96 0.96 0.95 0.94 0.96 0.93 0.96 0.94 0.93
CW  Total Cooling
 Capacity 
kW 28.3 33.2 42.8 57.3 62.3 55.3 60.2 67.9 71.7 91.3 98.1 108.2
CW Sensible Cooling
 Capacity 
kW 26.4 29.8 38.5 51.6 56.5 49.7 54.7 61.2 64.5 83.1 90 97.6
CW Sensible heat raio / 0.93 0.9 0.9 0.9 0.91 0.9 0.91 0.9 0.9 0.9 0.9 0.9
Water flow capacity m³/h 4.9 5.7 7.3 10 10.7 9.6 10.4 11.8 12.3 14.3 17.2 18.6
Pressure drop Kpa 54 78 95 89 102 82 96 65 71 100 109 126
Heating capacity
 (standard)
kW 6 6 6 9 9 9 9 9 9 12 12 12
Heating capacity
 (Max)
kW 12 12 12 18 18 18 18 18 18 24 24 24
Humidifying capacity
 (Standard)
Kg/h 6 8 8 10 10 10 10 10 10 12 12 12
Humidifying capacity 
 (Max)
Kg/h 8 8 8 15 15 15 15 15 15 15 15 15
Number of compressors Pcs 1 1 1 1 1 2 2 2 2 2 2 2
Number of fan Pcs 1 1 1 2 2 2 2 2 2 3 3 3
Full-load Current
(Air cooled and
 chilled water)
A 28.8 32.7 35.1 48.3 54.4 48.3 53.6 58.7 63.5 76.3 81.7 96.6
Full-load  Current
(Water cooled and
 chilled water)
A 26.1 27.3 29.7 42.9 49 38.4 48.2 50.6 55.4 68.2 73.6 85.8
Size of inlet and
outlet water pipes
mm 28 28 35 35 35 35 35 35 35 42 42 42
Unit Weight kg 400 470 480 640 650 700 730 800 810 1020 1040 1140
Unit Width mm 850 1200 1200 1650 1650 1650 1650 2010 2010 2460 2460 2810
Unit Depth mm 850 850 850 850 850 850 850 850 850 850 850 850
Unit Height mm 1960 1960 1960 1960 1960 1960 1960 1960 1960 1960 1960 1960
Note :
● Parameter table
    Air/water cooled unit data based on 24°C,50%RH indoor return air temperature.
    Chilled water unit data based on 24°C,50%RH indoor return air temperature。The inlet and outlet water temperature of chilled water are 7°C and 12°C。
    Electirc heating adopts three-level hierarchical control
The power supply type:380`415V/3p/50Hz
We can provide other customized product.If you need more information,please contact us.
Specifications are subject to change without prior notice

Cookie Policy