Home >  OEM/ODM > OEM/ODM Services > ups> Online Transformerless UPS> YDC3300 10kVA-20kVA(UL/CSA Certificated)

YDC3300
10-20kVA
 
YDC3300 series UPS compliant with UL/CSA standards is aviable now! Equipped with three-level inverter topology, it results in high energy-saving and reliability. With higher power density, smaller footprint, it takes the leading position in the UPS industry with same power capacity; Adopting unique power unit redundancy design technology, decrease the abnormity risk of system after single-point failure, greatly increase the system reliability. For user, it is your best choice with high investment rate.

Features

·High power density design 
·N+Xparallel redundancy, maximum 4 units 
.Onlline double conversion with DSP contro 
.Cold start 
·Wide input voltage range:72~159Vac . 
·Multiple protection function:short-circuitoverload,overheat 



Technical Specification

MODEL YDC3310S/H YDC3315S/H YDC3320S/H
Capacity 10kVA / 10kW 15kVA / 15kW 20kVA / 20kW
INPUT
Nominal voltage 208/120Vac or 220/127Vac (3Ph+N+PE)
Operating voltage range 96~159Vac (Full load); 72~159Vac (50% load)
Operating frequency range 40~70Hz (50/60Hz Auto-Sensing)
Power factor 0.99
Bypass voltage range Max. voltage: 20% (Optional 10%, 15%, 20%) Min. voltage: 30% (Optional 10%, 20%, 30%)
Frequency protection range 50/60Hz±10%
ECO range Same as bypass
Harmonic distortion (THDi) 2% Non linear load
OUTPUT
Output voltage 208/120Vac or 220/127Vac (3Ph+N+PE)
Voltage regulation ±1%
Power factor 1
Output frequency Line mode ±1%/±2%/±4%/±5%/±10% of the rated frequency (Optional)
Bat.  mode 50/60 (±0.1%)Hz
  AC mode to Bat.mode 0ms
Transfer time Inverter to Bypass 0ms
Output waveform Pure Sinewave
   
Crest factor 3:01
Harmonic distortion (THDv) 1% Linear load
3% Non linear load
Overload AC mode 110%, last 60min; 125%, last 10min; 150%, last 1min;150% turn to bypass immediately
Bat.mode 110%, last 10min; 125%, last 1min; 150%, last 5s;150% shutdown UPS immediately
EFFICIENCY
Efficiency up to 94%
BATTERY
Battery voltage Standard unit ±120Vdc (20pcs 12V9AH) (2×20pcs 12V9AH,    
3×20pcs ±120Vdc (2×20pcs 12V9AH) ±120Vdc (3×20pcs 12V9AH)
 12V9AH optional) (3×20pcs 12V9AH optional)
Long run unit ±96 /±108 /±120 /±132 /±144Vdc
Charge Current Standard unit 1.35A (2.7/4.05A optional) 2.7A (4.05A optional) 4.05A
Long run unit 20A Max.
PHYSICAL
Dimension Standard unit 250×900×868mm
W×D×H Long run unit 250×580×655mm
Net weight 136kg/77kg 188kg/78kg 239kg/79kg
ENVIRONMENTAL
Operating temperature 040
Storage temperature -2555
Humidity range 095% (non-condensing)
Altitude <1500m, derating required when>1500m
Noise level 55dB 58dB
STANDARDS
Safety UL1778, CSA 22.2-107.3-14
EMC FCC Part 15 Subpart B, ANSI C63.4 2014
Energy star Energy star 2.0





Contact US Now


Cookie Policy

By continuing to use this website, you agree to our use of cookies.Read our privacy policy>