Modular UPS-Kstar HPM  Family
40-1000kVA
 


In order to save the wasted power of underutilized, over-size ordinary UPS, and obtain "N+1" redundancy to ensure the critical system has high power availability, data centers now choose modular UPS as their first choice for critical power protection. With compact size, high efficiency and easy expansion according to power requirements. Modular UPS systems are growing fast in the three-phase market. 

The HPM series is a modular uninterruptible power supply (UPS) for medium - and large-sized data centers. It features high efficiency (96%) and a high input factor of 0.99, minimizing UPS energy consumption. The modular design and the N+X parallel redundancy technology, making the expansion & management easier as well as reduce initial acquisition costs.

It supports hot-swappable and reduces the maintenance time to 5 minutes and improves system availability. The maximum capacity can be expanded to 1000kva according to future needs, helping to lower initial investment.


 
General Features

● Adopting digital control design, and the control system is more reliable

● High input factor 0.99 and output factor 1.

 3-level topology design, efficiency is up to 96% 

 Support parallel expansion for cabinet, and  parallel expansion is up to 4-6 cabinets.

 Batteries number of each group can be selected from 30 pieces to 50 pieces.

 With 7 inches (standard) and 10 inches (optional) colorful touch LCD screen

Technical Specification

Module Model HPM3300E-RM-40 HPM3300E-RM-50
Cabinet Model HPM3300E-200/320/400 HPM3300E-200/300/400/500/600/800/1000
Cabinet capacity (VA) 200k~400k 200k~1000k
Module capacity (VA) 40k 50k
Max. Number  05/8/10 4/6/8/10/12/16/20
INPUT
Nominal voltage 380/400/415Vac, (3Ph+N+PE)
Operating voltage range 138~305Vacfor 40% Load; 305~485Vac for 100% Load;
Operating frequency range 40Hz-70Hz
Power factor ≥0.99
Harmonic distortion (THDi) ≤3% (100% linear load)
Bypass voltage range Max. voltage:220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%)

Min. voltage: -45% (optional-10%, -15%, -20%, -30%)
Bypass Frequency range Frequency protection range: ±10%
Power Walk In Support
Generator input Support
OUTPUT
Rated voltage 380/400/415Vac, (3Ph+N+PE)
Power factor 1
Voltage regulation ±1%
Output frequency Line Mode Synchronize with input, when the input frequency >±10%(±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz)
Bat. Mode (50/60±0.1%)Hz
Crest factor 0.125694444
Harmonic distortion (THDv) ≤1% with linear load; ≤3% with nonlinear load
Efficiency up to 96%
BATTERY
Battery voltage Optional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc(30/32/34/36/38/40/42/44/46/48/50pcs optional);
 360Vdc~600Vdc (30~50 pcs, 36 pcs default, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8)
Power module charge current 20A (Max.)
SYSTEM FEATURES
Transfer time Utility to Battery : 0ms; Utility to bypass: 0ms
Overload Line Mode ≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately.
Bypass Mode 135% overload for long term; >1000% overload for 100 ms
Overheat Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Low battery voltage Alarm and Switch off
Self-diagnostics Upon Power On and Software Control
Backfeed Support
EPO Shut down UPS immediately (turn to bypass optional)
Battery  Advanced Battery Management
Noise suppression Complies with EN62040-3
Audible & Visual alarms Line Failure, Battery Low, Overload, System Fault
Status LED & LCD display Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault
Reading on the LCD display
Input, Output, Battery, Command, Setting, Maintenance
Communication interface
RS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional)
ENVIRONMENTAL
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 0~95% (non condensing)
Altitude <1500m, derating required when >1500m
Noise level(from 1M distance) <68dB <73dB 
PHYSICAL
Dimension              WxD×H (mm) UPS cabinet
(S / F)
200/320kVA: 600×850×2000
400kVA: 1200×850×2000
200/300/400kVA: 600×850×2000
Power module 440×620×130
Net weight (kg) UPS cabinet
(S / F)
210~460 200kVA: 240; 300kVA: 260; 400kVA: 290;
500kVA: 480; 600kVA: 540; 800kVA: 960;
1000kVA: 1050 
Power module 33 34
STANDARDS
Safety IEC/EN62040-1, IEC/EN62477-1
EMC IEC/EN62040-2 (IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8)
       