Home >  Products > Data Center Infrastructure > Integrated Solutions> Modular Data Center (Room Type)> Integrated data center module|Prefabricated modular data center
IDM Micro Module Data Center Solution
IDM integrates cabinets, power supply and distribution system, cooling system, monitoring system, cabling system. As an All-In-One solution, IDM features quick deployment, energy Efficiency, smart management, safety and reliability
General Features

● Safety and Reliability

N+1/2N redundant design. The continuous power supply with back up battary guarantees stable IT equipment operation.

·Multi-stage automatic alarm function. Real-time system condition monitoring.

· Containment top panel can be opened by the fire system.

●Smart management

· Centralized monitoring platform makes us know the data center environment, power and temperature & humidity status in real-time.

· Powerful reporting capabilities.

· 365 days 7x24-hour unattended, remote monitoring. Minimize IT operation and maintenance costs.

●Energy-efficient

· Sealing hot or cold ventilation channels, greatly reduced the energy consumption.

· Inrow air conditioner close to heat source delivering air flow accurately to where desired.

· Efficient modular UPS.

· High density. A single cabinet supports a maximum 15 kW to meets various customer requirements.

●Quick Deployment

· Full integration of IT cabinet, UPS, battary, power distribution and precision cooling system.

· Modular components following international standards are quick to play within 7 days and greatly shorten the business on line cycle.

· Efficient modular UPS.

· Can be installed on a concrete floor, which greatly simplifies the corresponding engineering tasks.

Technical Specification
Mode IDM-16CS IDM-20CS IDM-16CB IDM-20CB IDM-16CT IDM-20CT IDM-16CF IDM-20CF
Structure and cabinets
Installation area(m²) ≥24 ≥30 ≥24 ≥30 ≥24 ≥30 ≥24 ≥30
Installation height(m) 2.6
Cabinet size
(W*D*H)mm
600*1100*2000(42U)
Power
Total IT capacity
(KW)
55 75 80 104 90 130 120 165
Redundant
architecture
N+X
Power format Input:380V/3P;Output:380V/3P
UPS power(KVA) 100 120 140 160 140 180 200 200
Backup time(min) 10、15、30、60、120、240min
Cooling
Redundant
architecture
N+1
Cooling Capacity
(KW)
23 25 23 40
Width(mm) 300 400 300 600
Monitoring
Temperature and
humidity sensors
Sdandard configuration two,can local precision monitoring
according to customer requirement
Smoke sensors 2
Leak detection Yes
Camera 2
UPS Yes
Power distribution monitoring Yes
AC monitoring Yes
KVM Optional
Notes IDM product solutions can be customized depending on the number of
cabinetspower densities power modes,
different backup time,UPS,Air conditioning

Cookie Policy