UDC
10kVA-20kVA
UDC 10-20kVA is an online double-conversion UPS providing consistent sine-wave power to your critical equipment. It supports personal computers, networks, servers, VoIP and telecommunications. With full digital control, ECO mode and compact design, it features high reliablity and energy savings. Optional external battery pack can be connected for longer backup time to keep your applications safe and running smoothly at all times.
General Features
● N+X parallel redundancy
● Online double conversion with DSP control
● Input current harmonic: <30%
● Optimization battery group, the quantity of battery:16/18/20 pieces(optional)
● Output power factor 0.9
● Wide input voltage range: 120~276Vac
● Wide input frequency range
● Support generator input
● ECO mode operation for energy saving
● Self-testing when UPS startup
● Options: SNMP card/Relay card/Parallel card
● Cold start
Technical Specification
MODEL | UDC9310S | UDC9310H | UDC9315S | UDC9315H | UDC9320S | UDC9320H | |
Capacity (VA/Watts) | 10K/9K | 10K/9K | 15K/13.5K | 15K/13.5K | 20K/18K | 20K/18K | |
INPUT | |||||||
Nominal Voltage | 220/230/240Vac | ||||||
Operating Voltage Range | 120~276Vac | ||||||
Frequency Range | 50Hz:45~55Hz;60Hz:54~66Hz(auto sensing) | ||||||
Power Factor | ≥0.99 | ||||||
Max.voltage: 220V: +25%(optional +10%,+15%,+20% ) 230V: +20% (optional +10%,+15%) | |||||||
Bypass voltage range | 240V: +15% (optional +10%) Min.voltage: -45% (optional -20%,-30%) | ||||||
Bypass frequency range | Frequency protection range:±10% | ||||||
ECO range | Same as the bypass | ||||||
Harmonic distortion (THDi) | <30%(100% linear load) | ||||||
Generator input | Support | ||||||
OUTPUT | |||||||
Output Voltage | 220/230/240Vac | ||||||
Power Factor | 0.9 | ||||||
Voltage Regulation | ±1% | ||||||
Frequency | Line Mode | ±1%/±2%/±4%/±5%/±10% of the rated frequency(optional) | |||||
Bat. Mode | 50/60(±0.1)Hz | ||||||
Crest Factor | 3:01 | ||||||
Harmonic Distortion (THDv) | ≤2% with linear load ;≤5% with non-linear load | ||||||
Efficiency | >93% | ||||||
BATTERY | |||||||
Battery voltage | ±96/108/120Vdc(optional) | ||||||
Capacity (standard unit) | 12V-7Ah/9Ah | ||||||
Typical recharging time | 6~8 hours (to 90% of full capacity) | ||||||
Charging current | 1A(Standard unit); Long run unit Max.current10A(charging current can be set according to battery capacity installed) | ||||||
SYSTEM FEATURES | |||||||
Transfer time | Mains to battery:0ms; Mains to bypass:0ms | ||||||
Overload | Line Mode | Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, >150% turn to bypass mode immediately | |||||
Bypass Mode | 63A(Breaker) | ||||||
Short circuit | Hold whole system | ||||||
Overheat | Line Mode: Turn to Bypass; Bat. Mode: Shut down UPS immediately | ||||||
Battery low | Alarm and switch off | ||||||
Self-diagnostics | Upon power on and software control | ||||||
Battery | Advanced battery management | ||||||
Audible & Visual alarms | Line failure, Battery low, Overload, System fault | ||||||
LED & LCD display | Line mode, Bat. mode, Eco mode, Bypass mode, Battery under voltage, Overload & UPS fault | ||||||
LCD display | Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, | ||||||
Inner temperature & Remaining battery backup time | |||||||
Communication interface | RS232,USB,SNMP card(optional), Parallel card(optional), Relay card (optional) | ||||||
ENVIRONMENT | |||||||
Operating temperature | 0℃~40℃ | ||||||
Storage temperature | '-25℃~55℃ | ||||||
Humidity range | '0~95% (non-condensing) | ||||||
Altitude | < 1500m | ||||||
Noise level | <55dB | ||||||
PHYSICAL(Output PF 1.0) | |||||||
Dimension W×D×H (mm) | Standard model:250*710*810 ; long run model:220*535*435 | ||||||
Net weight (kg) | Standard model:98kg ; long run model:27kg | ||||||
STANDARDS | |||||||
Safety | IEC/EN62040-1,IEC/EN60950-1 | ||||||
EMC | IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8 |