Home >  OEM/ODM > OEM/ODM Services > ups> Online Transformer Base UPS> EPOWER-L (10kVA-120kVA)

EPOWER-L
10-120kVA
 
EPOWER-L is a transformer-based UPS of KSTAR, both input and output are 3 phase. The output power factor is 0.8. This ups can work in paralle and expand its power capacity. This series UPS is high reliable and have good impact resistance, it can suppply safe and reliable protection for load.

General Features

● Online double conversion

● Full DSP control

● High power factor:0.9

● Wide input adaptability:(380Va/400Vac/415Vac) (-25%/+20%)

● Optimized battery management,self-test&lexible battery configuration 

● N+X parallel redundancy

● Strong overload capability:110%/125%/150% overload for 60/10/1min.

● Power walk in

● Generator mode

● LBS synchronization

● Multi-protection

● User-friendly network management


Technical Specification
MODEL EP10-L EP20-L EP30-L EP40-L EP60-L EP80-L  EP100-L EP120-L 
Capacity
 (VA/Watts)
10kVA / 8kW   20kVA / 16kW  30kVA / 24kW 40kVA / 32kW 60kVA /48kW 80kVA/ 64kW 100kVA/ 80kW  120kVA/ 96kW 
INPUT    
Operating 
voltage
 range 
380/400/415Vac (-25% / +20% ), (3Ph+N+PE)   
Operating
 frequency 
range
 50/60Hz(±5%)   
Power Factor >0.97 (with filter)   
OUTPUT     
Output Voltage 380/400/415Vac (±1%)   
Output frequency  50/60Hz (±0.05%)   
Harmonic
 Distortion 
(THDv)
<3% with linear load   
Crest factor 3:1 (max)   
Efficiency ≥90.5%  ≥91.5%   
BYPASS   
Rated voltage 380/400/415Vac   
Rated frequency 50/60Hz(auto-sensing)
Voltage
 protection
 range 
Upper limit: +20% (+10%,+15%,+20% adjustable)
Lower limit: -40% (-10%, -20%, -30%, -40% adjustable)
   
Frequency 
protection
 range
±10% (±2.5%, ±5%,±10%, ±20% adjustable)   
BATTERY   
Battery voltage  384Vdc ( 360~384Vdc )   
SYSTEM FEATURES   
Transfer time 0ms (Line mode →Battery mode)   
Overload ≤110%/60min ,≤125%/10min ,≤150%/1min,to Bypass   
LED display Input, Inverter, Bypass, Battery, Output, Status   
LCD display I/O voltage, frequency, power, power factor, battery voltage, current, battery status,
 load percentage, UPS status, history record
   
Communication
 interface
Dry contact, RS232, RS485, SNMP card (Optional)   
Optional   Harmonic filter, SNMP adapter, LBS cables, battery temperature sensor,Bypass current-sharing inductor   
ENVIRONMENT   
Operating 
Temperature
0℃~40℃   
Storage 
temperature
-25~55℃   
Humidity range 0~95% (non-condensing)   
Altitude  <1500m   
Noise level  <58dB <65dB     
PHYSICAL    
Dimension
 W×D×H (mm)
350×650×1050 430×830×1100   720×675×1400 890×775×1600   
Net weight (kg) 148 163 230 255 386 426 625    685   
STANDARDS    
Safety  IEC/EN 62040-1;IEC/EN 60950-1
Performance  IEC 62040-3    
EMC IEC/EN 62040-2;IEC 61000-2-2;IEC 61000-4-2;IEC 61000-4-3;IEC 61000-4-4; IEC 61000-4-5;IEC 61000-4-6;IEC 61000-4-8;IEC 61000-4-11;   