Home >  OEM/ODM > OEM/ODM Services > ups> Modular UPS> HPM3300E Sub Rack Module Series(10kVA-150kVA)

HPM3300E(10kVA-150kVA)
10kVA-150kVA
 
Kstar online rack modular UPS HPM3300E is a 3-phase modular UPS system designed for 19” rack integration. With modular design,compact size,it is easy to integrate,install and expand, it provides maximum availability and power protection in a flexible design leaving free space for other rack-mounted devices.


General Features

● Modular design, including power module, bypass module, monitoring module, can be easily integrated in MDC or customized cabinet.

● Width input voltage range, line voltage range is 138-485V,

● High input power factor, it is up to 0.99.

● Three level topology design, efficiency is up to 95.8%.

● THDi<3% (100% nonlinear load), THDi<5% (50% non-linear load)

● Sleeping mode to save power

● Support parallel expanded operation: maximum is 6 units

● Support sharing batteries for the UPS in parallel.

● Batteries number of each group can be selected from 30 pieces to 50 pieces.

● Large charging current can meet the requirement of long time backup.

 Output power factor is 1.0, UPS can supply power to 100% unbalance load.

 High adaptability for load, it can connect full inductive load or capacitive load.

 7 inches colorful touch screen

 Support RS485, SNMP, Dry contact card , support RJ 45 interface and CAN interface.

● Support upgrade of CAN of power module inside of the cabinet.


Technical Specification

Model HPM3300E-60 HPM3300E-120 HPM3300E-150
UPS cabinet 30k~60k / 30k~60k 30k~120k / 30k~120 30k~150k / 30k~150k
Max. Number 2 4 5+1
Module HPM3300E-RM-30 (30k / 30k)
Model HPM3300E-50 HPM3300E-100 HPM3300E-150
UPS cabinet 25k~50k / 25k~50k 25k~100k / 25k~100k 25k~150k / 25k~150k
Max. Number 2 4 5+1
Module HPM3300E-RM-25 (25k / 25k)
Model HPM3300E-40 HPM3300E-80 HPM3300E-120
UPS cabinet 20k~40k / 20k~40k 20k~80k / 20k~80k 10k~120k / 10k~120k
Max. Number 2 4 5+1
Module HPM3300E-RM-20 (20k / 20k)
Model HPM3300E-30 HPM3300E-60 HPM3300E-90
UPS cabinet 15k~30k / 15k~30k 15k~60k / 15k~60k 10k~90k / 10k~90k
Max. Number 2 4 5+1
Module HPM3300E-RM-15 (15k / 15k)
Model HPM3300E-20 HPM3300E-40 HPM3300E-60
UPS cabinet 10k~20k / 10k~20k 10k~40k / 10k~40k 10k~60k / 10k~60k
Max. Number 2 4 5+1
Module HPM3300E-RM-10 (10k / 10k)
INPUT  
Nominal voltage 380/400/415Vac, (3Ph+N+PE)
Operating voltage range 138~305Vac for 40% Load; 305~485Vac for 100% Load;
Operating frequency range 40Hz-70Hz
Power factor ≥0.99
Harmonic distortion (THDi) 3% (100% linear load)
Bypass voltage range Max. voltage:220V: +25%(optional +10%,+15%,+20% ) ; 230V: +20%(optional +10%,+15% ) ;240V: +15% (optional +10%)
Min. voltage: -45% (optional-10%, -20%,-30%)
Bypass Frequency range Frequency protection range: ±10%
Generator input Support
Backfeed protection Support
OUTPUT  
Rated voltage 380/400/415Vac, (3Ph+N+PE)
Power factor 1
Voltage regulation ±1%
Output Line Mode synchronize with input, when the input frequency >±10%(±1%/±2%/±3%/±4%/±5% optional),output 50/60(±0.1Hz)
frequency Bat. Mode (50/60±0.1%)Hz
Crest factor 3:01
Harmonic distortion (THD) ≤2% with linear load; ≤4% with nonlinear load
Efficiency UP to 95.8%
BATTERY  
  Optional Voltage:±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional)360Vdc~600Vdc (30~50 pcs), 36 pcs default, 36~50 pcs fully output; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8)
Battery voltage
Power module Charge Current 18A (Max.)
UPS cabinet Max. Charge Current 36A   72A 108A
SYSTEM FEATURES  
Transfer time Utility to Battery : 0ms; Utility to bypass: 0ms
Overload Line Mode ≤110%,60min;≤125%,10min;≤150%,1min;to bypass.>150% Shut down Immediately.
Bypass Mode 135% overload for long term; >1000% overload for 100 ms
Overheat Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Low battery voltage Alarm and Switch off
Self-diagnostics Upon Power On and Software Control
EPO(optional) Shut down UPS immediately
Battery   Advanced Battery Management  
Noise suppression Complies with EN62040-3
Audible & Visual alarms Line Failure, Battery Low, Overload, System Fault
Status LED & LCD display Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault
Reading on the LCD display Input, Output, Battery, Command, Setting, Maintenance
Communication interface CAN,RS485,Parallel, Dry contact port, Relay card(optional), SNMP card(optional),Battery temperature sensor(optional)
ENVIRONMENTAL  
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 0~95% (non condensing)
Altitude < 1500m
Noise level(from 1M distance) <58dB <60dB <62dB
PHYSICAL  
Dimension        
W×HxD (mm) UPS cabinet 485×353(8U)×850   485×575(13U)×850 485×752(17U)×850
  440x86 (2U)x620
  Power module  
Net weight (kg) UPS cabinet 142   153 295
  Power module 21
STANDARDS  
Audible & Visual alarms IEC/EN62040-1,IEC/EN60950-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4- 5,IEC61000-4-6,IEC61000-4-8
 