Modular UPS-HPM Family
10-150kVA
With a 7-inch colour touch screen, hot-swappable design, HPM3300E modular UPS features high efficiency (95.8%), high power density, easy scaling, scaling on demand, Parallel redundancy function and occupies only a small amount of floor area and provides safe, reliable, and clear environmentally friendly power to loads.
The series' N+X module and built-in system redundancy maintain a steady, reliable source of energy. It can provide the highest level of power protection and has been widely used in various industries such as IT rooms, data centers, banking, healthcare, insurance, and telecommunications.
General Features
● Modular design, including power module, bypass module, monitoring module, which means it can be easily integrated in MDC or customized cabinet.
● Flexible power module: 10/15/20/25/30kVA ((2U))
● High input power factor, it is up to 0.99.
● Width input voltage range:line voltage range is 138-485V, UPS would be derating when input voltage is below 305V.
● Parallel redundant configurations:failure of one module will not impact system or site operation.
● Three level topology design, efficiency is up to 95.8%.
● Sleeping Mode to save energy.
● Support parallel expanded operation: maximum is 6 units, Support sharing batteries for the UPS in parallel.
General Features
Module Model | HPM3300E-RM-10 | |||
Cabinet Model | HPM3300E-20 | HPM3300E-40 | HPM3300E-60 | |
Cabinet capacity (VA) | 10k~20k | 10k~40k | 10k~60k | |
Module capacity (VA) | 10k | |||
Max. Number | 2 | 4 | 6 | |
Module Model | HPM3300E-RM-15 | |||
Cabinet Model | HPM3300E-30 | HPM3300E-60 | HPM3300E-90 | |
Cabinet capacity (VA) | 15k~30k | 15k~60k | 15k~90k | |
Module capacity (VA) | 15k | |||
Max. Number | 2 | 4 | 6 | |
Module Model | HPM3300E-RM-20 | |||
Cabinet Model | HPM3300E-40 | HPM3300E-80 | HPM3300E-120 | |
Cabinet capacity (VA) | 20k~40k | 20k~80k | 20k~120k | |
Module capacity (VA) | 20k | |||
Max. Number | 2 | 4 | 6 | |
Module Model | HPM3300E-RM-25 | |||
Cabinet Model | HPM3300E-50 | HPM3300E-100 | HPM3300E-150 | |
Cabinet capacity (VA) | 25k~50k | 25k~100k | 25k~150k | |
Module capacity (VA) | 25k | |||
Max. Number | 2 | 4 | 6 | |
Module Model | HPM3300E-RM-30 | |||
Cabinet Model | HPM3300E-60 | HPM3300E-120 | HPM3300E-150 | |
Cabinet capacity (VA) | 30k~60k | 30k~120k | 30k~150k | |
Module capacity (VA) | 30k | |||
Max. Number | 2 | 4 | 5+1 | |
INPUT | ||||
Nominal voltage | 380/400/415Vac, (3Ph+N+PE) | |||
Operating voltage range | 138~305Vac for 40% Load; 305~485Vac for 100% Load; | |||
Operating frequency range | 40Hz-70Hz | |||
Power factor | ≥0.99 | |||
Harmonic distortion (THDi) | ≤3% (100% linear load) | |||
Bypass voltage range | Max. voltage:220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%) Min. voltage: -45% (optional-10%, -15%, -20%, -30%) |
|||
Bypass frequency range | Frequency protection range: ±10% | |||
Power Walk In | Support | |||
Generator input | Support | |||
OUTPUT | ||||
Rated voltage | 380/400/415Vac, (3Ph+N+PE) | |||
Power factor | 1.0 | |||
Voltage regulation | ±1% | |||
Output frequency | Line Mode | Synchronize with input, when the input frequency >±10%(±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz) | ||
Bat. Mode | (50/60±0.1%)Hz | |||
Crest factor | 3:1 | |||
Harmonic distortion (THDv) | ≤1% with linear load; ≤3% with nonlinear load | |||
Efficiency | up to 95.8% | |||
BATTERY | ||||
Battery voltage | Optional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc(30/32/34/36/38/40/42/44/46/48/50pcs optional); 360Vdc~600Vdc (30~50 pcs, 36 pcs default, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8) |
|||
Power module charge current | 18A (Max.) | |||
SYSTEM FEATURES | ||||
Transfer time | Utility to Battery : 0ms; Utility to bypass: 0ms | |||
Overload | Line Mode | ≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. | ||
Bypass Mode | 135% overload for long term; >1000% overload for 100 ms | |||
Overheat | Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately | |||
Low battery voltage | Alarm and Switch off | |||
Self-diagnostics | Upon Power On and Software Control | |||
Backfeed | Support | |||
EPO | Shut down UPS immediately (turn to bypass optional) | |||
Battery | Advanced Battery Management | |||
Noise suppression | Complies with EN62040-3 | |||
Audible & Visual alarms | Line Failure, Battery Low, Overload, System Fault | |||
Status LED & LCD display | Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault | |||
Reading on the LCD display | Input, Output, Battery, Command, Setting, Maintenance | |||
Communication interface | RS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional) | |||
ENVIRONMENTAL | ||||
Operating temperature | 0℃~40℃ | |||
Storage temperature | -25℃~55℃ | |||
Humidity range | 0~95% (non condensing) | |||
Altitude | <1500m, derating required when >1500m | |||
Noise level(from 1M distance) | <58dB | <60dB | <62dB | |
PHYSICAL | ||||
Dimension W×D×H (mm) | UPS cabinet | 485×850×353(8U) | 485×850×575(13U) | 485×850×752(17U) |
Power module | 440×620×86(2U) | |||
Net weight (kg) | UPS cabinet | 69 | 79 | 98 |
Power module | 10kVA: 19; 15~30kVA: 21 | |||
STANDARDS | ||||
Safety | IEC/EN62040-1, IEC/EN62477-1 | |||
EMC | IEC/EN62040-2 (IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8) | |||
Specifications are subject to change without prior notice. |