Modular UPS-HPM  Family
10-150kVA
   
With a 7-inch colour touch screen, hot-swappable design, HPM3300E modular UPS features high efficiency (95.8%), high power density, easy scaling, scaling on demand, Parallel redundancy function and occupies only a small amount of floor area and provides safe, reliable, and clear environmentally friendly power to loads.  

The series' N+X module and built-in system redundancy maintain a steady, reliable source of energy. It can provide the highest level of power protection and  has been widely used in various industries such as IT rooms, data centers, banking, healthcare, insurance, and telecommunications.



General Features

● Modular design, including power module, bypass module, monitoring module, which means it can be easily integrated in MDC or customized cabinet. 

 Flexible power module: 10/15/20/25/30kVA ((2U))

 High input power factor, it is up to 0.99.

 Width input voltage range:line voltage range is 138-485V, UPS would be derating when input voltage is below 305V. 

 Parallel redundant configurations:failure of one module will not impact system or site operation. 

 Three level topology design, efficiency is up to 95.8%.

● Sleeping Mode to save energy.

 Support parallel expanded operation: maximum is 6 units, Support sharing batteries for the UPS in parallel.


General Features


Module Model HPM3300E-RM-10
Cabinet Model HPM3300E-20 HPM3300E-40 HPM3300E-60
Cabinet capacity (VA) 10k~20k 10k~40k 10k~60k
Module capacity (VA) 10k
Max. Number 2 4 6
Module Model HPM3300E-RM-15
Cabinet Model HPM3300E-30 HPM3300E-60 HPM3300E-90
Cabinet capacity (VA) 15k~30k 15k~60k 15k~90k
Module capacity (VA) 15k
Max. Number 2 4 6
Module Model HPM3300E-RM-20
Cabinet Model HPM3300E-40 HPM3300E-80 HPM3300E-120
Cabinet capacity (VA) 20k~40k 20k~80k 20k~120k
Module capacity (VA) 20k
Max. Number 2 4 6
Module Model HPM3300E-RM-25
Cabinet Model HPM3300E-50 HPM3300E-100 HPM3300E-150
Cabinet capacity (VA) 25k~50k 25k~100k 25k~150k
Module capacity (VA) 25k
Max. Number 2 4 6
Module Model HPM3300E-RM-30
Cabinet Model HPM3300E-60 HPM3300E-120 HPM3300E-150
Cabinet capacity (VA) 30k~60k 30k~120k 30k~150k
Module capacity (VA) 30k
Max. Number 2 4 5+1
INPUT
Nominal voltage 380/400/415Vac, (3Ph+N+PE)
Operating voltage range 138~305Vac for 40% Load; 305~485Vac for 100% Load;
Operating frequency range 40Hz-70Hz
Power factor ≥0.99
Harmonic distortion (THDi) ≤3% (100% linear load)
Bypass voltage range Max. voltage:220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%)
Min. voltage: -45% (optional-10%, -15%, -20%, -30%)
Bypass frequency range Frequency protection range: ±10%
Power Walk In Support
Generator input Support
OUTPUT
Rated voltage 380/400/415Vac, (3Ph+N+PE)
Power factor 1.0
Voltage regulation ±1%
Output frequency Line Mode Synchronize with input, when the input frequency >±10%(±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz)
Bat. Mode (50/60±0.1%)Hz
Crest factor 3:1
Harmonic distortion (THDv) ≤1% with linear load; ≤3% with nonlinear load
Efficiency up to 95.8%
BATTERY
Battery voltage Optional Voltage: ±180/192/204/216/228/240/252/264/276/288/300Vdc(30/32/34/36/38/40/42/44/46/48/50pcs optional);
 360Vdc~600Vdc (30~50 pcs, 36 pcs default, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8)
Power module charge current 18A (Max.)
SYSTEM FEATURES
Transfer time Utility to Battery : 0ms; Utility to bypass: 0ms
Overload Line Mode ≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately.
Bypass Mode 135% overload for long term; >1000% overload for 100 ms
Overheat Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Low battery voltage Alarm and Switch off
Self-diagnostics Upon Power On and Software Control
Backfeed Support
EPO Shut down UPS immediately (turn to bypass optional)
Battery Advanced Battery Management
Noise suppression Complies with EN62040-3
Audible & Visual alarms Line Failure, Battery Low, Overload, System Fault
Status LED & LCD display Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault
Reading on the LCD display Input, Output, Battery, Command, Setting, Maintenance
Communication interface RS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional)
ENVIRONMENTAL
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 0~95% (non condensing)
Altitude <1500m, derating required when >1500m
Noise level(from 1M distance) <58dB <60dB <62dB
PHYSICAL
Dimension              W×D×H (mm) UPS cabinet 485×850×353(8U) 485×850×575(13U) 485×850×752(17U)
Power module 440×620×86(2U)
Net weight (kg) UPS cabinet 69 79 98
Power module 10kVA: 19; 15~30kVA: 21
STANDARDS
Safety IEC/EN62040-1, IEC/EN62477-1
EMC IEC/EN62040-2 (IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8)
Specifications are subject to change without prior notice.