HPM3300E-T series UPS is developed as a high frequency large capacity tower UPS which can solve most of the power supply problems, such as blackout, over-voltage, voltage sudden drop, oscillating of decreasing extent, high voltage pulse, voltage fluctuation, surge, inrush current, harmonic distortion (THD), noise interference and frequency fluctuation. It has a strong load capacity and can be matched with full inductive load or capacitive load. The UPS can be used in various applications ranging from computer equipment, automatic equipment, large and medium-sized data centers, bank/security settlement centers, communication systems to industrial equipment.
General Features
●138-485 Vac wide input voltage range to minimize battery use
●High input power factor up to 0.99
●Three level topology design, efficiency is up to 96.5%
●Support parallel expanded operation: maximum is 8 units
●Smart sleeping mode for energy saving and prolong the life time of the system
●Support shared batteries for UPS in parallel
●Power saving with high input power factor up to 0.99
●VRLA & Lithium battery supportable
●Strong load capacity,1.0 power factor for 100% unbalanced load
●Can connect full inductive load or capacitive load
●Compatible with generator
●LBS function:2 independent UPS system can work in synchronization to enchances reliability
●Superior MTTR (Meantime to repair) & Short shutdown time in maintenance
●Touch-screen Super-large LCD display
●Resistant to high humidity, high heat, dust and salt spray
Technical Specification
Model | HPM3300E-200-T | HPM3300E-250-T | HPM3300E-300-T | HPM3300E-400-T | HPM3300E-500-T | HPM3300E-600-T | HPM3300E-800-T | HPM3300E-1000-T | HPM3300E-1200-T | |
Capacity (VA) | 200k | 250k | 300k | 400k | 500k | 600k | 800k | 1000k | 1200k | |
INPUT | ||||||||||
Nominal voltage | 380/400/415Vac, (3Ph+N+PE) | |||||||||
Operating voltage range | 138~305Vac for 40% load; 305~485Vac for 100% load | |||||||||
Operating frequency range | 40Hz~70Hz | |||||||||
Power factor | ≥0.99 | |||||||||
Harmonic distortion (THDi) | ≤3% (100% linear load) | |||||||||
Bypass voltage range | Max. voltage:220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%) | |||||||||
Min. voltage: -45% (optional-10%, -15%, -20%, -30%) | ||||||||||
Bypass frequency range | Frequency protection range: ±10% | |||||||||
Power Walk In | Support | |||||||||
Generator input | Support | |||||||||
OUTPUT | ||||||||||
Rated voltage | 380/400/415Vac, (3Ph+N+PE) | |||||||||
Power factor | 1 | |||||||||
Voltage regulation | ±1% | |||||||||
Output | Line mode | Synchronize with input, when the input frequency >±10%(±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz) | ||||||||
frequency | Bat. mode | (50/60±0.1%)Hz | ||||||||
Crest factor | 3:1 | |||||||||
Harmonic distortion (THDv) | ≤2% with linear load; ≤4% with nonlinear load | |||||||||
Efficiency | up to 96.5% | |||||||||
BATTERY | ||||||||||
Battery voltage | VRLA battery | 360Vdc~600Vdc (30~50pcs continuously adjustable, 30pcs default, 36~50pcs no power derating; 32~35pcs output power factor 0.9; 30/31pcs output power factor 0.8) |
||||||||
Lithium battery | 512Vdc | |||||||||
Power module charge current | 80A(Max.) | 100A(Max.) | 140A(Max.) | 180A(Max.) | 200A(Max.) | 280A(Max.) | 340A(Max.) | 400A (Max.) | ||
SYSTEM FEATURES | ||||||||||
Transfer time | Utility to Battery : 0ms; Utility to Bypass: 0ms | |||||||||
Overload | Line mode | ≤110%, 60min; ≤125%, 10min; ≤150%,1min; to bypass.>150% Shut down Immediately. | ||||||||
Bypass mode | 30℃: 135% overload for long term; 40℃: 125% overload for long term; >1000% overload for 100 ms | |||||||||
Overheat | Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately | |||||||||
Low battery voltage | Alarm and Switch off | |||||||||
Self-diagnostics | Upon Power On and Software Control | |||||||||
Backfeed protection | Support | |||||||||
EPO (optional) | Shut down UPS immediately (turn to bypass optional) | |||||||||
Battery | Advanced Battery Management | |||||||||
Noise suppression | Complies with EN62040-3 | |||||||||
Audible & visual alarms | Line Failure, Battery Low, Overload, System Fault | |||||||||
Status LED & LCD display | Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault | |||||||||
Reading on the LCD display | Input, Output, Battery, Command, Setting, Maintenance | |||||||||
Communication interface | RS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional) | |||||||||
ENVIRONMENTAL | ||||||||||
Operating temperature | 0℃~40℃ | |||||||||
Storage temperature | -25℃~55℃ | |||||||||
Humidity range | 0~95% (non condensing) | |||||||||
Altitude | <1500m, derating required when >1500m | |||||||||
Noise level | <63dB | <65dB | <70dB | <70dB | <73dB | <74dB | ||||
PHYSICAL | ||||||||||
Dimension W×D×H (mm) | S | 600×850×2000 | 1200×850×2000 | 2000×850×2000 | 2200×850×2000 | |||||
F | ||||||||||
Net weight (kg) | 406 | 440 | 460 | 548 | 959 | 1060 | 1422 | 1658 | 1880 | |
STANDARDS | ||||||||||
Safety | IEC/EN62040-1, IEC/EN62477-1 | |||||||||
EMC | IEC/EN62040-2 (IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8) | |||||||||