HPM Modular UPS with Lithium Batteries
50-1200kVA
The HPM family is a modular UPS designed to offer the highest possible availability. The power of a single UPS unit can be increased up to 1200 kW and the system can include up to 8 units in parallel. This modular 3 phase UPS also provides one of the highest efficiency ratings in its class and delivers better power protection and quality to the load.The hot-swappable function can reduce the maintenance time to 5 minutes and improves system availability. It provides you higher power density, smaller footprint, and easy-scaling.
General Features
● 138-485 Vac wide input voltage range to minimize battery use
● High input power factor up to 0.99
● 3-level topology design, efficiency is up to 96.5%
● Support parallel expanded operation:maximum is 8 units
● Smart sleeping mode for energy saving and prolong the life time of the system
● User-friendly 7-inch and 10-inch LCD touch screen for easy UPS operation
Technical Specification
Module Model | HPM3300E-RM-50 | |||||||
Cabinet Model | HPM3300E-200 | HPM3300E-300 | HPM3300E-400 | HPM3300E-500 | HPM3300E-600 | HPM3300E-800 | HPM3300E-1000 | |
Cabinet capacity (VA) | 200k | 300k | 400k | 500k | 600k | 800k | 1000k | |
Module capacity (VA) | 50k | |||||||
Max. number | 4 | 6 | 8 | 10 | 12 | 16 | 20 | |
INPUT | ||||||||
Nominal voltage | 380/400/415Vac, (3Ph+N+PE) | |||||||
Operating voltage range | 138~305Vac for 40% Load; 305~485Vac for 100% Load; | |||||||
Operating frequency range | 40Hz-70Hz | |||||||
Power factor | ≥0.99 | |||||||
Harmonic distortion (THDi) | ≤3% (100% linear load) | |||||||
Bypass voltage range | Max. voltage:220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%) | |||||||
Min. voltage: -45% (optional-10%, -15%, -20%, -30%) | ||||||||
Bypass frequency tracking range | ±10% | |||||||
Power Walk In | Support | |||||||
Generator input | Support | |||||||
OUTPUT | ||||||||
Rated voltage | 380/400/415Vac, (3Ph+N+PE) | |||||||
Power factor | 1 | |||||||
Voltage regulation | ±1% | |||||||
Output | Line mode | Synchronize with input, when the input frequency >±10%(±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz) | ||||||
frequency | Bat. mode | (50/60±0.1%)Hz | ||||||
Crest factor | 3 :1 | |||||||
Harmonic distortion (THDv) | ≤2% with linear load; ≤4% with nonlinear load | |||||||
Efficiency | up to 96.5% | |||||||
BATTERY | ||||||||
Battery voltage | VRLA battery | 360Vdc~600Vdc (30~50pcs continuously adjustable, 30pcs default, 36~50pcs no powerderating; 32~35pcs output power factor 0.9; 30/31pcs output power factor 0.8) | ||||||
Lithium battery | 512Vdc | |||||||
Power module charge current | 20A (Max.) | |||||||
SYSTEM FEATURES | ||||||||
Transfer time | Utility to Battery : 0ms; Utility to bypass: 0ms | |||||||
Overload | Line mode | ≤110%, 60min; ≤125%, 10min; ≤150%,1min to bypass; >150%, shut down immediately | ||||||
Bypass mode | 30℃: 135% overload for long term; 40℃: 125% overload for long term; >1000% overload for 100 ms | |||||||
Overheat | Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately | |||||||
Low battery voltage | Alarm and Switch off | |||||||
Self-diagnostics | Upon Power On and Software Control | |||||||
Backfeed protection | Support | |||||||
EPO (optional) | Shut down UPS immediately (turn to bypass optional) | |||||||
Battery | Advanced Battery Management | |||||||
Noise suppression | Complies with EN62040-3 | |||||||
Audible & visual alarms | Line Failure, Battery Low, Overload, System Fault | |||||||
Status LED & LCD display | Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault | |||||||
Reading on the LCD display | Input, Output, Battery, Command, Setting, Maintenance | |||||||
Communication interface | RS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional) | |||||||
ENVIRONMENTAL | ||||||||
Operating temperature | 0℃~40℃ | |||||||
Storage temperature | -25℃~55℃ | |||||||
Humidity range | 0~95% (non condensing) | |||||||
Altitude | <1500m, derating required when >1500m | |||||||
Noise level | <65dB | <66dB | <68dB | <70dB | <73dB | |||
PHYSICAL | ||||||||
Dimension | UPS cabinet (S) | 600×850×2000 | 600×850×2000 | 1200×850×2000 | 2000×850×2000 | |||
UPS cabinet (F) | 1200×850×2000 | |||||||
Power module | 440×620×130 | |||||||
UPS cabinet | 270 | 290 | 310/470 | 650 | 720 | 980 | 1080 | |
Net weight (kg) | Power module | 34 | ||||||
STANDARDS | ||||||||
Safety | IEC/EN62040-1, IEC/EN62477-1 | |||||||
EMC | IEC/EN62040-2 (IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8) |
Module Model | HPM3300E-RM-60 | ||||||
Cabinet Model | HPM3300E-300 | HPM3300E-480 | HPM3300E-600 | HPM3300E-840 | HPM3300E-1080 | HPM3300E-1200 | |
Cabinet capacity (VA) | 300k | 480k | 600k | 840k | 1080k | 1200k | |
Module capacity (VA) | 60K | ||||||
Max. number | 5 | 8 | 10 | 14 | 18 | 20 | |
INPUT | |||||||
Nominal voltage | 380/400/415Vac, (3Ph+N+PE) | ||||||
Operating voltage range | 138~305Vac for 40% Load; 305~485Vac for 100% Load; | ||||||
Operating frequency range | 40Hz-70Hz | ||||||
Power factor | ≥0.99 | ||||||
Harmonic distortion (THDi) | ≤3% (100% linear load) | ||||||
Bypass voltage range | Max. voltage:220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%) | ||||||
Min. voltage: -45% (optional-10%, -15%, -20%, -30%) | |||||||
Bypass frequency tracking range | ±10% | ||||||
Power Walk In | Support | ||||||
Generator input | Support | ||||||
OUTPUT | |||||||
Rated voltage | 380/400/415Vac, (3Ph+N+PE) | ||||||
Power factor | 1 | ||||||
Voltage regulation | ±1% | ||||||
Output | Line mode | Synchronize with input, when the input frequency >±10%(±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz) | |||||
frequency | Bat. mode | (50/60±0.1%)Hz | |||||
Crest factor | 3 : 1 | ||||||
Harmonic distortion (THDv) | ≤2% with linear load; ≤4% with nonlinear load | ||||||
Efficiency | up to 96.5% | ||||||
BATTERY | |||||||
Battery voltage | VRLA battery | 360Vdc~600Vdc (30~50pcs continuously adjustable, 30pcs default, 36~50pcs no powerderating; 32~35pcs output power factor 0.9; 30/31pcs output power factor 0.8) | |||||
Lithium battery | 512Vdc | ||||||
Power module charge current | 20A (Max.) | ||||||
SYSTEM FEATURES | |||||||
Transfer time | Utility to Battery : 0ms; Utility to bypass: 0ms | ||||||
Overload | Line mode | ≤110%, 60min; ≤125%, 10min; ≤150%,1min to bypass; >150%, shut down immediately | |||||
Bypass mode | 30℃: 135% overload for long term; 40℃: 125% overload for long term; >1000% overload for 100 ms | ||||||
Overheat | Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately | ||||||
Low battery voltage | Alarm and Switch off | ||||||
Self-diagnostics | Upon Power On and Software Control | ||||||
Backfeed protection | Support | ||||||
EPO (optional) | Shut down UPS immediately (turn to bypass optional) | ||||||
Battery | Advanced Battery Management | ||||||
Noise suppression | Complies with EN62040-3 | ||||||
Audible & visual alarms | Line Failure, Battery Low, Overload, System Fault | ||||||
Status LED & LCD display | Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault | ||||||
Reading on the LCD display | Input, Output, Battery, Command, Setting, Maintenance | ||||||
Communication Interface | RS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional) | ||||||
ENVIRONMENTAL | |||||||
Operating temperature | 0℃~40℃ | ||||||
Storage temperature | -25℃~55℃ | ||||||
Humidity range | 0~95% (non condensing) | ||||||
Altitude | <1500m, derating required when >1500m | ||||||
Noise level | <66dB | <70dB | <73dB | ||||
PHYSICAL | |||||||
Dimension | UPS cabinet (S) | 600×850×2000 | 1200×850×2000 | 2000×850×2000 | 2000×850×2000 | ||
UPS cabinet (F) | |||||||
Power module | 440×620×130 | ||||||
UPS cabinet | 290 | 650 | 720 | 980 | 1080 | 1200 | |
Net weight (kg) | Power module | 34 | |||||
STANDARDS | |||||||
Safety | IEC/EN62040-1, IEC/EN62477-1 | ||||||
EMC | IEC/EN62040-2 (IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8) |