Home >  Products > Data Center Infrastructure > UPS> Lithium-ion UPS> HPM3300E Modular UPS with Lithium Batteries
HPM Modular UPS with Lithium Batteries
50-1200kVA
 

The HPM family is a modular UPS designed to offer the highest possible availability. The power of a single UPS unit can be increased up to 1200 kW and the system can include up to 8 units in parallel. This modular 3 phase UPS also provides one of the highest efficiency ratings in its class and delivers better power protection and quality to the load.The
hot-swappable function can reduce the maintenance time to 5 minutes and improves system availability. It provides you higher power density, smaller footprint, and easy-scaling. 
General Features

● 138-485 Vac wide input voltage range to minimize battery use

● High input power factor up to 0.99

 3-level topology design, efficiency is up to 96.5% 

 Support parallel expanded operation:maximum is 8 units

 Smart sleeping mode for energy saving and prolong the life time of the system

 User-friendly 7-inch and 10-inch LCD touch screen for easy UPS operation

Technical Specification     

Module Model HPM3300E-RM-50
Cabinet Model HPM3300E-200 HPM3300E-300 HPM3300E-400 HPM3300E-500 HPM3300E-600 HPM3300E-800 HPM3300E-1000
Cabinet capacity (VA) 200k 300k 400k 500k 600k 800k 1000k
Module capacity (VA) 50k
Max. number 4 6 8 10 12 16 20
INPUT  
Nominal voltage 380/400/415Vac, (3Ph+N+PE)
Operating voltage range 138~305Vac for 40% Load; 305~485Vac for 100% Load;
Operating frequency range  40Hz-70Hz
Power factor ≥0.99
Harmonic distortion (THDi) ≤3% (100% linear load)
Bypass voltage range  Max. voltage:220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%)
Min. voltage: -45% (optional-10%, -15%, -20%, -30%)
Bypass frequency tracking range ±10%
Power Walk In Support
Generator input Support
OUTPUT
Rated voltage 380/400/415Vac, (3Ph+N+PE)
Power factor 1
Voltage regulation ±1%
Output Line mode Synchronize with input, when the input frequency >±10%(±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz)
frequency Bat. mode (50/60±0.1%)Hz
Crest factor   3 1
Harmonic distortion (THDv) ≤2% with linear load; ≤4% with nonlinear load
Efficiency up to 96.5%
BATTERY
Battery voltage VRLA battery 360Vdc~600Vdc (30~50pcs continuously adjustable, 30pcs default, 36~50pcs no powerderating; 32~35pcs output power factor 0.9; 30/31pcs output power factor 0.8)
Lithium battery 512Vdc
Power module charge  current 20A (Max.)
SYSTEM FEATURES
Transfer time Utility to Battery : 0ms; Utility to bypass: 0ms
Overload Line mode ≤110%, 60min; ≤125%, 10min; ≤150%,1min to bypass; >150%, shut down immediately
  Bypass mode 30℃: 135% overload for long term; 40℃: 125% overload for long term; >1000% overload for 100 ms
Overheat Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Low battery voltage Alarm and Switch off
Self-diagnostics Upon Power On and Software Control
Backfeed protection Support
EPO (optional) Shut down UPS immediately (turn to bypass optional)
Battery Advanced Battery Management
Noise suppression Complies with EN62040-3
Audible & visual alarms Line Failure, Battery Low, Overload, System Fault
Status LED & LCD display Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault
Reading on the LCD display Input, Output, Battery, Command, Setting, Maintenance
Communication interface RS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional)
ENVIRONMENTAL
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 0~95% (non condensing)
Altitude <1500m, derating required when >1500m
Noise level <65dB <66dB <68dB <70dB   <73dB  
PHYSICAL
Dimension UPS cabinet (S) 600×850×2000 600×850×2000 1200×850×2000 2000×850×2000
  UPS cabinet (F) 1200×850×2000
  Power module 440×620×130
  UPS cabinet 270 290 310/470 650 720 980 1080
Net weight (kg) Power module 34
STANDARDS
Safety IEC/EN62040-1, IEC/EN62477-1
EMC IEC/EN62040-2 (IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8)
  
Module Model HPM3300E-RM-60
Cabinet Model HPM3300E-300 HPM3300E-480 HPM3300E-600 HPM3300E-840 HPM3300E-1080 HPM3300E-1200
Cabinet capacity (VA) 300k  480k  600k 840k 1080k 1200k
Module capacity (VA) 60K
Max. number 5 8 10 14 18 20
INPUT
Nominal voltage 380/400/415Vac, (3Ph+N+PE)
Operating voltage range 138~305Vac for 40% Load; 305~485Vac for 100% Load;
Operating frequency range   40Hz-70Hz
Power factor ≥0.99
Harmonic distortion (THDi) ≤3% (100% linear load)
Bypass voltage range Max. voltage:220V: +25% (optional+10%, +15%, +20% ); 230V: +20% (optional +10%, +15% ); 240V: +15% (optional +10%)
  Min. voltage: -45% (optional-10%, -15%, -20%, -30%)
Bypass frequency tracking range ±10%
Power Walk In Support
Generator input Support
OUTPUT
Rated voltage 380/400/415Vac, (3Ph+N+PE)
Power factor 1
Voltage regulation ±1%
Output Line mode Synchronize with input, when the input frequency >±10%(±1%/±2%/±3%/±4%/±5% optional), output 50/60 (±0.1Hz)
frequency Bat. mode (50/60±0.1%)Hz
Crest factor   3  : 1
Harmonic distortion (THDv) ≤2% with linear load; ≤4% with nonlinear load
Efficiency up to 96.5%
BATTERY
Battery voltage VRLA battery 360Vdc~600Vdc (30~50pcs continuously adjustable, 30pcs default, 36~50pcs no powerderating; 32~35pcs output power factor 0.9; 30/31pcs output power factor 0.8)
Lithium battery 512Vdc
Power module charge  current 20A (Max.)
SYSTEM FEATURES
Transfer time Utility to Battery : 0ms; Utility to bypass: 0ms
Overload Line mode ≤110%, 60min; ≤125%, 10min; ≤150%,1min to bypass; >150%, shut down immediately
Bypass mode 30℃: 135% overload for long term; 40℃: 125% overload for long term; >1000% overload for 100 ms
Overheat Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Low battery voltage Alarm and Switch off
Self-diagnostics Upon Power On and Software Control
Backfeed protection Support
EPO (optional) Shut down UPS immediately (turn to bypass optional)
Battery Advanced Battery Management
Noise suppression Complies with EN62040-3
Audible & visual alarms Line Failure, Battery Low, Overload, System Fault
Status LED & LCD display Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault
Reading on the LCD display Input, Output, Battery, Command, Setting, Maintenance
Communication Interface  RS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional)
ENVIRONMENTAL
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 0~95% (non condensing)
Altitude <1500m, derating required when >1500m
Noise level <66dB <70dB <73dB
PHYSICAL
Dimension UPS cabinet (S) 600×850×2000 1200×850×2000 2000×850×2000 2000×850×2000
UPS cabinet (F)
  Power module 440×620×130
  UPS cabinet 290 650 720 980 1080 1200
Net weight (kg) Power module 34
STANDARDS
Safety IEC/EN62040-1, IEC/EN62477-1
EMC IEC/EN62040-2 (IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8)